Restoration of directional overcurrent relay coordination in distributed generation systems utilizing fault current limiter

作者:
W El-KhattamTS Sidhu

关键词:
distributed power generation distribution networks fault current limiters overcurrent protection relay protection FCL impedance type directional overcurrent relay coordination distributed generation systems fault current limiter fault locations

摘要:
A new approach is proposed to solve the directional overcurrent relay coordination problem, which arises from installing distributed generation (DG) in looped power delivery systems (PDS). This approach involves the implementation of a fault current limiter (FCL) to locally limit the DG fault current, and thus restore the original relay coordination. The proposed restoration approach is carried out without altering the original relay settings or disconnecting DGs from PDSs during fault. Therefore, it is applicable to both the current practice of disconnecting DGs from PDSs, and the emergent trend of keeping DGs in PDSs during fault. The process of selecting FCL impedance type (inductive or resistive) and its minimum value is illustrated. Three scenarios are discussed: no DG, the implementation of DG with FCL and without FCL. Various simulations are carried out for both single- and multi-DG existence, and different DG and fault locations. The obtained results are reported and discussed.