220 kV旁代主变操作引起差动保护动作分析
Analysis of Bypassing 220 kV Transformer Caused Differential Protection Action
摘要:
大兴变旁代主变过程导致差动保护动作,主变三侧开关跳闸,经短接CT电流端子模拟试验,确认为五防钥匙误碰CT电流端子,导致AB相短路,出现差流启动差动保护。本文提出加强现场防误碰措施、规范二次操作,以提高运行人员技术水平。
Abstract:
The process of bypassing transformer of Daxing leads to differential protection action and transformer’s three side of switch trip. According to the simulation experiment of short circuit CT terminals, it is sure that the thing that five-prevention key falsely touches the current terminals leads to short circuit phase A and B, the appearance of differential current and the start of differential protection. The paper proposes to enhance the measure of anti false touch and specify secondary operation, in order to improve the technology level of operators.
参考文献
[1]
|
国家电力调度通信中心 (2000) 电力系统继电保护典型故障分析. 中国电力出版社, 北京.
|
[2]
|
贺家李 (2004) 电力系统继电保护原理. 增订版, 中国电力出版社, 北京.
|
[3]
|
国家电力调度通信中心 (2000) 电力系统继电保护实用技术问答. 第二版, 中国电力出版社, 北京.
|
[4]
|
王磊, 王越男 (2005) 220 kV变电站变压器差动保护动作原因分析. 佳木斯大学学报, 16, 34-38
|
[5]
|
袁文嘉, 李敏霞, 姬希军 (2009) 一起区外故障引起主变差动保护动作的分析. 电力系统保护与控制, 23, 130-132.
|
[6]
|
戴志辉, 王增平 (2010) 继电保护可靠性研究综述. 电力系统保护与控制, 15, 161-167.
|